Portable Fire Extinguisher Guide |
Fire Protection Association Australia Website www.fpaa.com.au |
| CLASS A |
CLASS B |
CLASS C |
CLASS E |
CLASS F |
CLASS D |
| Two colour schemes for fire extinguishers exist |
EXTING- UISHANT |
Wood Paper Plastics |
Flammable & Combustible Liquids |
Flammable Gases |
Electrically Energised Equipment |
Cooking Oils and Fats |
For fire involving combustible metals use specials purpose extinguisher |
| PRE 1999 |
FROM 1999 |
 |
 |
WATER |
YES |
NO |
NO |
NO |
NO |
Dangerous if used on flammable liquid, engergised electrical equipment and cooking oils/fat fires |
 |
 |
WET CHEMICAL |
YES |
NO |
NO |
NO |
YES |
Dangerous if used on engerised electrical equipment |
 |
 |
FOAM |
YES |
YES |
NO |
NO |
LIMITED |
Dangerous if used on engerised electrical equipment |
 |
 |
POWDER |
YES
(ABE)
NO
(BE) |
YES
(ABE)
YES
(BE) |
YES
(ABE)
YES
(BE) |
YES
(ABE)
YES
(BE) |
NO
(ABE)
LIMITED
(BE) |
Dangerous if used on engerised electrical equipment |
 |
 |
CARBON DIOXIDE |
LIMITED |
LIMITED |
LIMITED |
YES |
LIMITED |
Dangerous if used on engerised electrical equipment |
 |
 |
VAPORISING LIQUID |
YES |
LIMITED |
LIMITED |
YES |
NO |
Dangerous if used on engerised electrical equipment |
LIMITED indicates that the extinguishant is not the agent of choice for the class of fire, but that it may have a limited extinguishing capability.
Solvents such as alcohol or acetone mix with water and therefore require special foam
Green text indicates the class or classes in which agent is most effective. |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Eversafe EAD Range: The cylinders are deep drawn from centre welded cold rolled steel and are hydrostatically tested to twice the fire extinguisher working pressure. The hot forged, brass operating valve is fitted with a pressure indicator and incorporates facility to enable 'in service' testing as required by AS 1851.1. Coated with epoxy powder, the cylinder offers corrosion resistance and passes the 480 hours salt spray test.
The EVERSAFE range of dry powder fire extinguishers are charged with specially fluidised and siliconised mono ammonium phosphate powder which offers resistance to compaction where the fire extinguisher is installed in a location subject to vibration and are safe and effective for use on Class A and B fires. Being an electrically non-conductive agent, EVERSAFE dry powder fire extinguishers are also safe to use on fires (Class E) involving equipment carrying live electrical current.
EAD Series
| TECHNICAL SPECIFICATION |
| MODEL |
EAD-1s |
EAD-2s |
EAD-2sh |
EAD-3s |
EAD-4s |
EAD-6s |
EAD-9s |
| TYPE |
STORED PRESSURE TYPE |
| PROPELLANT |
DRY NITROGEN (N2) |
| CAPACITY |
1.0 kg |
2.0 kg |
2.0 kg |
3.0 kg |
4.0 kg |
6.0 kg |
9.0 kg |
| VALVE |
CONTROLLABLE BRASS VALVE WITH PRESSURE INDICATOR |
| CYLINDER DIAMETER |
79 mm |
100 mm |
100 mm |
130 mm |
158 mm |
158 mm |
178mm |
| OVERALL HEIGHT |
330 mm |
380 mm |
410 mm |
490 mm |
470 mm |
560 mm |
620 mm |
| APPROX. FULL MASS |
2.2 kg |
3.75 kg |
4.0 kg |
5.75 kg |
7.5 kg |
10.00 kg |
14.25 kg |
| WORKING PRESSURE |
1200 kPa @ 23 +/- 2 c |
| TEST PRESSURE |
2.5 MPa |
| BURST PRESSURE |
6.9 MPa |
| APPROX. DISCHARGE TIME |
10 sec |
13 sec |
15 sec |
18 sec |
22 sec |
22 sec |
22 sec |
| FIRE RATING (STILL AIR) |
1A10B:E |
2A30B:E |
2A30B:E |
2A30B:E |
3A40B:E |
4A40B:E |
6A80B:E |
| COATING-INTERNAL |
STOVING EPOXY PRIMER |
| PAINT FINISH |
SIGNAL RED (R13) EPOXY POWDER COATING |
| MOUNTING |
PLASTIC VEHICLE BRACKET WALL BRACKET |
| DESIGN & MANUFACTURE |
AS/NZS 1841.5 |
Eversafe EAC Range: Our range of Carbon Dioxide fire Extinguishers are assembled in Australia under and Approved ISO 9001 Quality Management System using Australian Made, light alloy cylinders.
Carbon Dioxide is electrically non-conductive and is therefore ideal for use where electrical hazards exist. Carbon Dioxide fire extinguishers are further suited to risks involving sensitive electronic equipment because, as a clean gas, it will not leave a messy, potentially damaging residue. The 2.0kg model is fitted with a swivel elbow ad conical horn whilst the 3.5 and 5.0kg models are fitted with a hose and horn assembly.
EAC Series
| TECHNICAL SPECIFICATION |
| MODEL |
EAC 2 |
EAC 35 |
EAC 5 |
| TYPE |
CARBON DIOXIDE |
| CAPACITY |
2.0 kg |
3.5 kg |
5.0 kg |
| VALVE |
BRASS WITH CONTROLLABLE DISCHARGE |
| BODY DIAMETER |
111 mm |
140 mm |
152 mm |
| OVERALL HEIGHT |
540 mm |
585 mm |
675 mm |
| PROJECTION FROM WALL |
190 mm* |
155 mm |
160 mm |
| APPROX. FULL MASS** |
4.9 kg |
8.4 kg |
11.4 kg |
| CYLINDER TEST PRESSURE |
21.9 MPa |
20.7 MPa |
21.9 MPa |
| APPROX.DISCHARGE TIME |
15 sec |
11 sec |
13 sec |
| FIRE RATING (STILL AIR) |
5 B:E |
5 B:E |
5 B: E |
| PAINT FINSIH |
SIGNAL RED (R13) EPOXY PPOWDER COATING |
| MOUNTING |
METAL WALL BRACKET |
| DESIGN & MANUFACTURE |
AS/NZS 1841.6 |
* Includes Swivel Elbow Assembly
** Full Mass does not include swivel horn assembly or house and horn assembly.
Fire Hose Reel
(EA36R)
| TECHNICAL SPECIFICATION |
| MODEL |
EA36HR |
| Hose Length |
36 m |
| Hose Diameter |
19 mm ID |
| Burst Pressure |
>4 MPa |
| Drum Diameter |
562 mm |
| Nozzle |
Chrome Plated Brass |
| Nozzle Discharge |
Spray/ Jet |
| Min Discharge |
0.45 L/s @ 220 KPA |
| Bracket Type |
Quick Fit |
| Design & Manufacture To |
AS 1221 |
| Australian Standards for the maintenance of Fire Safety Equipment: |
| AS1851.1 |
1995 |
Portable Fire Extinguishers and Fire Blankets |
| AS1851.2 |
1995 |
Fire Hose Reels |
| AS1851.3 |
1997 |
Automatic Fire Sprinkler Systems |
| AS1851.4 |
1992 |
Fire Hydrant Installations |
| AS1851.5 |
1981 |
Automatic Smoke / Heat Venting Systems |
| AS1851.10 |
1989 |
Emergency Warning and Intercommunication Systems |
| AS1851.11 |
1991 |
Halon 1301 Total Flood Systems |
| AS1851.12 |
1995 |
Gaseous Fire Extinguishing Systems |
| AS1851.13 |
1995 |
Wheeled Fire Extinguishers |
| AS1851.14 |
1996 |
Pumpset Systems |
| AS1851.15 |
1997 |
Local Fire Alarm Systems |
| AS1851.16 |
1997 |
Pyrogen Fire Extinguishing Aerosol Systems |
|