United Fire Equipment Services, Fire Extinguishers, Hoses & Protection, Melbourne, Australia 

UFE United Fire Equipment Services
Home Portable Equipment Services & Maintenance Training Systems Contact Us
Portable Equipment - Specifications
Fire Protection Association Australia Portable Fire Extinguisher Guide Fire Protection Association Australia Website www.fpaa.com.au
CLASS A CLASS B CLASS C CLASS E CLASS F CLASS D
Two colour schemes for fire extinguishers exist EXTING- UISHANT Wood
Paper
Plastics
Flammable & Combustible Liquids Flammable Gases Electrically Energised Equipment Cooking Oils and Fats For fire involving combustible metals use specials purpose extinguisher
PRE 1999 FROM 1999
WATER YES NO NO NO NO Dangerous if used on flammable liquid, engergised electrical equipment and cooking oils/fat fires
WET CHEMICAL YES NO NO NO YES Dangerous if used on engerised electrical equipment
FOAM YES YES NO NO LIMITED Dangerous if used on engerised electrical equipment
POWDER YES
(ABE)

NO
(BE)
YES
(ABE)

YES
(BE)
YES
(ABE)

YES
(BE)
YES
(ABE)

YES
(BE)
NO
(ABE)

LIMITED
(BE)
Dangerous if used on engerised electrical equipment
CARBON DIOXIDE LIMITED LIMITED LIMITED YES LIMITED Dangerous if used on engerised electrical equipment
VAPORISING LIQUID YES LIMITED LIMITED YES NO Dangerous if used on engerised electrical equipment
LIMITED indicates that the extinguishant is not the agent of choice for the class of fire, but that it may have a limited extinguishing capability.
Solvents such as alcohol or acetone mix with water and therefore require special foam
Green text indicates the class or classes in which agent is most effective.



Eversafe EAD Range: The cylinders are deep drawn from centre welded cold rolled steel and are hydrostatically tested to twice the fire extinguisher working pressure. The hot forged, brass operating valve is fitted with a pressure indicator and incorporates facility to enable 'in service' testing as required by AS 1851.1. Coated with epoxy powder, the cylinder offers corrosion resistance and passes the 480 hours salt spray test.

The EVERSAFE range of dry powder fire extinguishers are charged with specially fluidised and siliconised mono ammonium phosphate powder which offers resistance to compaction where the fire extinguisher is installed in a location subject to vibration and are safe and effective for use on Class A and B fires. Being an electrically non-conductive agent, EVERSAFE dry powder fire extinguishers are also safe to use on fires (Class E) involving equipment carrying live electrical current.

EAD Series

TECHNICAL SPECIFICATION
MODEL EAD-1s EAD-2s EAD-2sh EAD-3s EAD-4s EAD-6s EAD-9s
TYPE STORED PRESSURE TYPE
PROPELLANT DRY NITROGEN (N2)
CAPACITY 1.0 kg 2.0 kg 2.0 kg 3.0 kg 4.0 kg 6.0 kg 9.0 kg
VALVE CONTROLLABLE BRASS VALVE WITH PRESSURE INDICATOR
CYLINDER DIAMETER 79 mm 100 mm 100 mm 130 mm 158 mm 158 mm 178mm
OVERALL HEIGHT 330 mm 380 mm 410 mm 490 mm 470 mm 560 mm 620 mm
APPROX. FULL MASS 2.2 kg 3.75 kg 4.0 kg 5.75 kg 7.5 kg 10.00 kg 14.25 kg
WORKING PRESSURE 1200 kPa @ 23 +/- 2 c
TEST PRESSURE 2.5 MPa
BURST PRESSURE 6.9 MPa
APPROX. DISCHARGE TIME 10 sec 13 sec 15 sec 18 sec 22 sec 22 sec 22 sec
FIRE RATING (STILL AIR) 1A10B:E 2A30B:E 2A30B:E 2A30B:E 3A40B:E 4A40B:E 6A80B:E
COATING-INTERNAL STOVING EPOXY PRIMER
PAINT FINISH SIGNAL RED (R13) EPOXY POWDER COATING
MOUNTING PLASTIC VEHICLE BRACKET WALL BRACKET
DESIGN & MANUFACTURE AS/NZS 1841.5




Eversafe EAC Range: Our range of Carbon Dioxide fire Extinguishers are assembled in Australia under and Approved ISO 9001 Quality Management System using Australian Made, light alloy cylinders.

Carbon Dioxide is electrically non-conductive and is therefore ideal for use where electrical hazards exist. Carbon Dioxide fire extinguishers are further suited to risks involving sensitive electronic equipment because, as a clean gas, it will not leave a messy, potentially damaging residue. The 2.0kg model is fitted with a swivel elbow ad conical horn whilst the 3.5 and 5.0kg models are fitted with a hose and horn assembly.

EAC Series

TECHNICAL SPECIFICATION
MODEL EAC 2 EAC 35 EAC 5
TYPE CARBON DIOXIDE
CAPACITY 2.0 kg 3.5 kg 5.0 kg
VALVE BRASS WITH CONTROLLABLE DISCHARGE
BODY DIAMETER 111 mm 140 mm 152 mm
OVERALL HEIGHT 540 mm 585 mm 675 mm
PROJECTION FROM WALL 190 mm* 155 mm 160 mm
APPROX. FULL MASS** 4.9 kg 8.4 kg 11.4 kg
CYLINDER TEST PRESSURE 21.9 MPa 20.7 MPa 21.9 MPa
APPROX.DISCHARGE TIME 15 sec 11 sec 13 sec
FIRE RATING (STILL AIR) 5 B:E 5 B:E 5 B: E
PAINT FINSIH SIGNAL RED (R13) EPOXY PPOWDER COATING
MOUNTING METAL WALL BRACKET
DESIGN & MANUFACTURE AS/NZS 1841.6

* Includes Swivel Elbow Assembly
** Full Mass does not include swivel horn assembly or house and horn assembly.




Fire Hose Reel (EA36R)

TECHNICAL SPECIFICATION
MODEL EA36HR
Hose Length 36 m
Hose Diameter 19 mm ID
Burst Pressure >4 MPa
Drum Diameter 562 mm
Nozzle Chrome Plated Brass
Nozzle Discharge Spray/ Jet
Min Discharge 0.45 L/s @ 220 KPA
Bracket Type Quick Fit
Design & Manufacture To AS 1221





Australian Standards for the maintenance of Fire Safety Equipment:
AS1851.1 1995 Portable Fire Extinguishers and Fire Blankets
AS1851.2 1995 Fire Hose Reels
AS1851.3 1997 Automatic Fire Sprinkler Systems
AS1851.4 1992 Fire Hydrant Installations
AS1851.5 1981 Automatic Smoke / Heat Venting Systems
AS1851.10 1989 Emergency Warning and Intercommunication Systems
AS1851.11 1991 Halon 1301 Total Flood Systems
AS1851.12 1995 Gaseous Fire Extinguishing Systems
AS1851.13 1995 Wheeled Fire Extinguishers
AS1851.14 1996 Pumpset Systems
AS1851.15 1997 Local Fire Alarm Systems
AS1851.16 1997 Pyrogen Fire Extinguishing Aerosol Systems

DNV Certification Logo
The fire protection specialists
Contact Us United Fire Equipment Services Pty Ltd., Melbourne, Australia
Home | Portable Equipment | Services & Maintenance | Training | Systems | Contact Us | Sitemap
Website Development & hosting by Exa Web site design Melbourne Australia
Today's date: Jan 7th, 2009
Exa